8-Wide I/O Carrier

مشخصات فنی

Brand Name:

EMERSON

Model Number:

VE4050S2K1C0 KJ4001X1-BE1

Alternate Part Number

12P0818X072

Condition:

100% Original

Dimensions

4.4 cm x 10.2 cm x 10.8 cm

Weight

0.2kg

Description

8-Wide I/O Carrier

Warranty:

12 Months

The EMERSON VE4050S2K1C0 KJ4001X1-BE1 12P0818X072 is an 8-Wide I/O Carrier designed for use in Emerson automation systems. This carrier supports multiple I/O modules and provides a reliable and robust interface for field connections.


Power Specifications

Local Bus Power: 12.6 VDC at 8 A

Bussed Field Power: 30 VDC at 6.5 A


Environmental Specifications
Ambient Temperature: -40°C to +70°C
Shock: 10 g half-sine wave for 11 ms
Vibration: 1 mm peak-to-peak from 2 to 13.2 Hz; 0.7 g from 13.2 to 150 Hz
Airborne Contaminants: Meets ISA-S71.04-1985 Airborne Contaminants Class G3 standards

Relative Humidity: 5 to 95% non-condensing


Important Usage Guidelines

Aspect

Guideline

Bussed Field Power

Must not be connected to a supply with a potential exceeding 30 VDC.

Removal and Insertion

Field power, whether supplied at the terminal or as bussed field power through the I/O carrier, must be turned off before removing or connecting the device.

De-energizing Requirements

Power must be turned off before disconnecting any carriers or LocalBus Extender cables.

Unoccupied Locations

A module cover (KJ4001X1-FA1) must be installed on any permanently unoccupied location on an I/O module carrier (where no I/O module or terminal block is intended).

Safety Precautions

The device must not be unplugged unless the system is de-energized or the area is confirmed to be safe.

Cable Length Limitations

The combined length of I/O carriers and LocalBus Extenders must not exceed 6.5 meters. Interconnecting cables between enclosures should be placed in conduit.


Maintenance and Adjustment

Serviceability: This unit has no user-serviceable parts and should not be disassembled for any reason.
Calibration: Calibration is not required.